kumpulan kode error ac mitsubishi lengkap dengan penjelasannya
Hallo sobat pada artikel kali ini saya ingin berbagi pengalaman pada saat menangani ac mitsubishi slim ini. Ketika unit AC mitsubishi ini sedang mengalami trouble maka akan menampilkan beberapa kode error.
simak dibawah ini ya
kumpulan kode error ac mitsubishi slim
code
|
Error detail
|
Inspected unit
|
Kode error EA
|
Mis-wiring of indoor
outdoor unit
Exceed the number of unit
indoor conection
|
outdoor
|
Kode error Eb
|
Mis-wiring of indoor
outdoor unit
Mis-wiring disconection
|
outdoor
|
Kode error EC
|
Start up time over
|
Outdoor
|
Kode error E6
|
Indoor outdoor unit
transmision error (signal receiving error)
|
Indoor
|
Kode error E7
|
Indoor outdoor unit
transmission error (transmitting error)
|
Indoor
|
Kode error E8
|
Indoor outdoor unit
transmission error (signal receiving error)
|
Outdoor
|
Kode error E9
|
Indoor outdoor unit
transmission error
( transmitting error)
|
outdoor
|
Kode error E0
|
Remote controller
transmission error (signal receiving error)
|
RC
|
Kode error E3
|
Remote controller
transmission error (transmitting error)
|
RC
|
Kode error E4
|
Remote controller
transmission error ( signal receiving error)
|
Indoor
|
Kode error E5
|
Remote controller
transmission error ( transmitting error)
|
Indoor
|
Kode error EF
|
M-NET transmission error
|
Indoor
|
Kode error EF
|
M-NET transmission error
|
Outdoor
|
Kode error Ed
|
Serial transmission error
|
Outdoor
|
Kode error P1
|
Abnormaly of room
temperature thermistor
|
Indoor
|
Kode error P2
|
Abnormaly of pipe
temperature thermistor liquid
|
Indoor
|
Kode error P4
|
Abnormaly of drain sensor
|
Indoor
|
Kode error P5
|
Malfunction of drain pump
machine
|
Indoor
|
Kode error P6
|
Freezing / overheating
protecting detect
|
Indoor
|
Kode error P8
|
Abnormaly of pipe
temperature
|
Indoor
|
Kode error P9
|
Abnormaly pipe temperature
thermistor cond/eva
|
Indoor
|
Kode error F1
|
Reverse phase detection
|
Outdoor
|
Kode error F2
|
L3 phase detection
|
Outdoor
|
Kode error F3
|
63 L conector open
|
Outdoor
|
Kode error F4
|
49C conector open
|
Outdoor
|
Kode error F9
|
Conector 2 or more open
|
Outdoor
|
Kode error FA
|
L2 phased open phase or 51
cm conector open
|
Outdoor
|
Kode error F7
|
Reverse phase detector
circuit fault
|
Outdoor
|
Kode error F8
|
Input circuit fault
|
Outdoor
|
Kode error U2
|
Abnormaly high discharging
temperature
|
Outdoor
|
Kode error U2
|
Inner thermostat (49C)
operation
|
Outdoor
|
Kode error U1
|
Abnormaly high preasurre
|
Outdoor
|
Kode error Ui
|
Direct cut operation
|
Outdoor
|
Kode error UE
|
High pressure error
|
Outdoor
|
Kode error UL
|
Abnormaly low preasure
|
Outdoor
|
Kode error UD
|
Overheat protection
|
Outdoor
|
Kode error U6
|
Compressor over current
(overload)cut off
|
Outdoor
|
Kode error UA
|
Compressor over current
(terminal relay operation)
|
Outdoor
|
Kode error UF
|
Compressor (start up
locked) cut off
|
Outdoor
|
Kode error UF
|
Compressor over current
(operating locked) cut off
|
Outdoor
|
Kode error UH
|
Current sensor error
|
Outdoor
|
Kode error U3
|
Discharged thermistor
short/open
|
Outdoor
|
Kode error U4
|
Outdoor thermistor
short/open
|
Outdoor
|